Total Vents:
22
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
11
Low / Intake Vents:
(Within Lower 1/3 of Attic)
11
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
4,000
Code Required Method:
1/300 (EXCEPTION)
Calculation:
4,000 ÷ 300 = 13.33 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
13.33
Calculation:
13.33 x 144 = 1,919.52 sq. in. of Code Required Ventilation
Square Inches Provided:
(22 x 88.87) = 1,955.14 sq. in.
concrete Tile Vents
Low Profile (Flat)
NET FREE VENTILATION AREA
1/8" Noncombustible, Corrosion-Resistant Wire Mesh 88.87 sq. in.
Figures based on independent evaluation reports.