Total Vents:
46
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
23
Low / Intake Vents:
(Within Lower 1/3 of Attic)
23
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
8,474
Code Required Method:
1/300 (EXCEPTION)
Calculation:
8,474 ÷ 300 = 28.25 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
28.25
Calculation:
28.25 x 144 = 4,068 sq. in. of Code Required Ventilation
Square Inches Provided:
(46 x 88.87) = 4,088.02 sq. in.
concrete Tile Vents
Low Profile (Flat)
NET FREE VENTILATION AREA
1/8" Noncombustible, Corrosion-Resistant Wire Mesh 88.87 sq. in.
Figures based on independent evaluation reports.