24
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
12
Low / Intake Vents:
(Within Lower 1/3 of Attic)
12
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
2,102
Code Required Method:
1/150 (EXCEPTION)
Calculation:
2,102 ÷ 150 = 14.01 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
14.01
Calculation:
14.01 x 144 = 2,017.44 sq. in. of Code Required Ventilation
Square Inches Provided:
(24 x 97.50) = 2,340 sq. in.
clay Tile Vents
High Profile (S)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 97.50 sq. in.