Total Vents:
60
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
30
Low / Intake Vents:
(Within Lower 1/3 of Attic)
30
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
4,500
Code Required Method:
1/150 (EXCEPTION)
Calculation:
4,500 ÷ 150 = 30 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
30
Calculation:
30 x 144 = 4,320 sq. in. of Code Required Ventilation
Square Inches Provided:
(60 x 72) = 4,320 sq. in.
concrete Tile Vents
Low Profile (Flat)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 72 sq. in.
Figures based on independent evaluation reports.