Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
800'
Required Method:
1/150
Calculation:
800 ÷ 150 = 5.33 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
5.33
Calculation:
5.33 x 144 = 767.52 sq. in of Code Required Ventilation
Square Inches Provided:
(8 x 98.75) = 790 sq. in
Square Inches Needed:
5.33 x 144 = 767.52 sq. in
Vent Placement
High / Exhaust Vents Needed:
4
Low / Intake Vents Needed:
4
Total Vents Needed:
8
Composition shingle
Low Profile (Tapered)
NET FREE VENTILATION AREA
Wire Mesh
98.75 sq. in
Figures based on independent evaluation reports.