Address:
5089 Lago Vista Way, Paradise, CA 95969
Total Vents:
14
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
7
Low / Intake Vents:
(Within Lower 1/3 of Attic)
7
Comp Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
2,530
Code Required Method:
1/300 (EXCEPTION)
Calculation:
2,530 ÷ 300 = 8.43 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
8.43
Calculation:
8.43 x 144 = 1,213.92 sq. in. of Code Required Ventilation
Square Inches Provided:
(14 x 98.75) = 1,382.50 sq. in.
Composition shingle
Low Profile (Tapered)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 98.75 sq. in.
Figures based on independent evaluation reports.
Vent Solutions
Questions?