Address:
VISTA DEL BOSQUE MURRIETA CA 92562
Total Vents:
54
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
27
Low / Intake Vents:
(Within Lower 1/3 of Attic)
27
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
4,775
Code Required Method:
1/150 (EXCEPTION)
Calculation:
4,775 ÷ 150 = 31.83 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
31.83
Calculation:
31.83 x 144 = 4,583.52 sq. in. of Code Required Ventilation
Square Inches Provided:
(54 x 86.25) = 4,657.50 sq. in.
clay Tile Vents
Medium Profile (M)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 86.25 sq. in.
Figures based on independent evaluation reports.