455 Jennileah Lane, San Marcos - Fire zone
Total Vents:
22
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
11
Low / Intake Vents:
(Within Lower 1/3 of Attic)
11
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
2,066
Code Required Method:
1/150 (EXCEPTION)
Calculation:
2,066 ÷ 150 = 13.77 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
13.77
Calculation:
13.77 x 144 = 1,982.88 sq. in. of Code Required Ventilation
Square Inches Provided:
(22 x 97.50) = 2,145 sq. in.
concrete Tile Vents
High Profile (S)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 97.50 sq. in.
Figures based on independent evaluation reports.