Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
19,454
Code Required Method:
1/300 (EXCEPTION)
Calculation:
19,454 ÷ 300 = 64.85 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
64.85
Calculation:
64.85 x 144 = 9,338.40 sq. in. of Code Required Ventilation
Square Inches Provided:
(96 x 97.50) = 9,360 sq. in.
clay Tile Vents
High Profile (S)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 97.50 sq. in.
Figures based on independent evaluation reports.