Address:
17380 Campillo Drive, San Diego - non fire zone
Total Vents:
12
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
6
Low / Intake Vents:
(Within Lower 1/3 of Attic)
6
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
1,217
Code Required Method:
1/150 (EXCEPTION)
Calculation:
1,217 ÷ 150 = 8.11 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
8.11
Calculation:
8.11 x 144 = 1,167.84 sq. in. of Code Required Ventilation
Square Inches Provided:
(12 x 97.50) = 1,170 sq. in.
concrete Tile Vents
High Profile (S)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 97.50 sq. in.
Figures based on independent evaluation reports.
Vent Solutions