Address:
6828 E Milagro Ave
Total Vents:
36
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
18
Low / Intake Vents:
(Within Lower 1/3 of Attic)
18
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
3,100
Code Required Method:
1/150 (EXCEPTION)
Calculation:
3,100 ÷ 150 = 20.67 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
20.67
Calculation:
20.67 x 144 = 2,976.48 sq. in. of Code Required Ventilation
Square Inches Provided:
(36 x 86.25) = 3,105 sq. in.
concrete Tile Vents
Medium Profile (M)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 86.25 sq. in.
Figures based on independent evaluation reports.
Vent Solutions