Total Vents:
54
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
27
Low / Intake Vents:
(Within Lower 1/3 of Attic)
27
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
5,400
Code Required Method:
1/150 (EXCEPTION)
Calculation:
5,400 ÷ 150 = 36 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
36
Calculation:
36 x 144 = 5,184 sq. in. of Code Required Ventilation
Square Inches Provided:
(54 x 98.75) = 5,332.50 sq. in.