Back to Vent Calculator
Print
Address:
5229 Shores Drive, Carlsbad - Non Fire Zone
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
1742'
Required Method:
1/150
Calculation:
1742 ÷ 150 = 11.61 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
11.61
Calculation:
11.61 x 144 = 1671.84 sq. in of Code Required Ventilation
Square Inches Provided:
(24 x 72) = 1728 sq. in
Square Inches Needed:
11.61 x 144 = 1671.84 sq. in
Vent Placement
High / Exhaust Vents Needed:
12
Low / Intake Vents Needed:
12
Total Vents Needed:
24
Composition shingle
Low Profile (Tapered)
NET FREE VENTILATION AREA
Wire Mesh
72 sq. in
Figures based on independent evaluation reports.