Address:
3907 Brighton Ave
Total Vents:
2
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
1
Low / Intake Vents:
(Within Lower 1/3 of Attic)
1
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
30
Code Required Method:
1/150 (EXCEPTION)
Calculation:
30 ÷ 150 = 0.20 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
0.20
Calculation:
0.20 x 144 = 28.80 sq. in. of Code Required Ventilation
Square Inches Provided:
(2 x 98.75) = 197.50 sq. in.
concrete Tile Vents
Low Profile (Flat)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 98.75 sq. in.
Figures based on independent evaluation reports.
Vent Solutions
Questions?