Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
814'
Required Method:
1/150
Calculation:
814 ÷ 150 = 5.43 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation
5.43
Calculation:
5.43 x 144 = 781.92 sq. in of Code Required Ventilation
Select Material and Determine Vents Required
Material:
Composition shingle
Placement
Square Inches Provided:
(12 x 72) = 864 sq. in
Square Inches Needed:
5.43 x 144 = 781.92 sq. in
High / Exhaust Vents Needed:
6
Low / Intake Vents Needed:
6
Total Vents Needed:
12
Material:
Composition shingle
Product:
Low Profile - "Tapered"
Comp Roof Drawing