Total Square Feet of Attic Space to be Ventilated:
1018'
Required Method:
1/300
Calculation:
1018 ÷ 300 = 3.39 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation
3.39
Calculation:
3.39 x 144 = 488.16 sq. in of Code Required Ventilation
Select Material and Determine Vents Required
Material:
concrete Tile
Placement
Square Inches Provided:
(6 x 97.5) = 585 sq. in
Square Inches Needed:
3.39 x 144 = 488.16 sq. in
High / Exhaust Vents Needed:
3
Low / Intake Vents Needed:
3
Total Vents Needed:
6
Material:
concrete Tile
Product:
High Profile - "S"