Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
2500'
Required Method:
1/150
Calculation:
2500 ÷ 150 = 16.67 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
16.67
Calculation:
16.67 x 144 = 2400.48 sq. in of Code Required Ventilation
Square Inches Provided:
(26 x 98.75) = 2567.5 sq. in
Square Inches Needed:
16.67 x 144 = 2400.48 sq. in
Vent Placement
High / Exhaust Vents Needed:
13
Low / Intake Vents Needed:
13
Total Vents Needed:
26
concrete Tile Vents
Low Profile (Flat)
NET FREE VENTILATION AREA
Wire Mesh
98.75 sq. in