Total Vents:
56
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
28
Low / Intake Vents:
(Within Lower 1/3 of Attic)
28
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
5,706
Code Required Method:
1/150 (EXCEPTION)
Calculation:
5,706 ÷ 150 = 38.04 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
38.04
Calculation:
38.04 x 144 = 5,477.76 sq. in. of Code Required Ventilation
Square Inches Provided:
(56 x 98.75) = 5,530 sq. in.
concrete Tile Vents
Low Profile (Flat)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 98.75 sq. in.
Figures based on independent evaluation reports.
Vent Solutions