Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
9500'
Required Method:
1/150
Calculation:
9500 ÷ 150 = 63.33 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation
63.33
Calculation:
63.33 x 144 = 9119.52 sq. in of Code Required Ventilation
Select Material and Determine Vents Required
Material:
concrete Tile
Placement
Square Inches Provided:
(106 x 86.25) = 9142.5 sq. in
Square Inches Needed:
63.33 x 144 = 9119.52 sq. in
High / Exhaust Vents Needed:
53
Low / Intake Vents Needed:
53
Total Vents Needed:
106
Material:
concrete Tile
Product:
Medium Profile - "M"
Tile Roof Drawing