Address:
601 Universe Blvd
Total Vents:
24
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
12
Low / Intake Vents:
(Within Lower 1/3 of Attic)
12
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
4,589
Code Required Method:
1/300 (EXCEPTION)
Calculation:
4,589 ÷ 300 = 15.30 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
15.30
Calculation:
15.30 x 144 = 2,203.20 sq. in. of Code Required Ventilation
Square Inches Provided:
(24 x 97.50) = 2,340 sq. in.
concrete Tile Vents
High Profile (S)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 97.50 sq. in.
Figures based on independent evaluation reports.
Vent Solutions
Questions?