Total Vents:
98
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
49
Low / Intake Vents:
(Within Lower 1/3 of Attic)
49
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
10,000
Code Required Method:
1/150 (EXCEPTION)
Calculation:
10,000 ÷ 150 = 66.67 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
66.67
Calculation:
66.67 x 144 = 9,600.48 sq. in. of Code Required Ventilation
Square Inches Provided:
(98 x 98.75) = 9,677.50 sq. in.
concrete Tile Vents
Low Profile (Flat)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 98.75 sq. in.
Figures based on independent evaluation reports.