Address:
9720 Camberley Circle, Orlando FL 32836
Total Vents:
64
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
32
Low / Intake Vents:
(Within Lower 1/3 of Attic)
32
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
6,396
Code Required Method:
1/150 (STANDARD)
Calculation:
6,396 ÷ 150 = 42.64 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
42.64
Calculation:
42.64 x 144 = 6,140.16 sq. in. of Code Required Ventilation
Square Inches Provided:
(64 x 98.75) = 6,320 sq. in.
concrete Tile Vents
Low Profile (Flat)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 98.75 sq. in.
Figures based on independent evaluation reports.