Total Vents:
24
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
12
Low / Intake Vents:
(Within Lower 1/3 of Attic)
12
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
4,127
Code Required Method:
1/300 (EXCEPTION)
Calculation:
4,127 ÷ 300 = 13.76 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
13.76
Calculation:
13.76 x 144 = 1,981.44 sq. in. of Code Required Ventilation
Square Inches Provided:
(24 x 88.87) = 2,132.88 sq. in.
concrete Tile Vents
Low Profile (Flat)
NET FREE VENTILATION AREA
1/8" Noncombustible, Corrosion-Resistant Wire Mesh 88.87 sq. in.
Figures based on independent evaluation reports.