Total Vents:
728
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
364
Low / Intake Vents:
(Within Lower 1/3 of Attic)
364
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
54,456
Code Required Method:
1/150 (EXCEPTION)
Calculation:
54,456 ÷ 150 = 363.04 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
363.04
Calculation:
363.04 x 144 = 52,277.76 sq. in. of Code Required Ventilation
Square Inches Provided:
(728 x 72) = 52,416 sq. in.
clay Tile Vents
Low Profile (Flat)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 72 sq. in.
Figures based on independent evaluation reports.