Address:
3451 W. CLANFIELD STREET ACTON, CA 93510
Total Vents:
14
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
7
Low / Intake Vents:
(Within Lower 1/3 of Attic)
7
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
1,257
Code Required Method:
1/150 (STANDARD)
Calculation:
1,257 ÷ 150 = 8.38 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
8.38
Calculation:
8.38 x 144 = 1,206.72 sq. in. of Code Required Ventilation
Square Inches Provided:
(14 x 97.50) = 1,365 sq. in.
concrete Tile Vents
High Profile (S)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 97.50 sq. in.
Figures based on independent evaluation reports.
Vent Solutions
Questions?