Address:
1707 Braeburn Road Altadena Ca 91001
Total Vents:
18
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
9
Low / Intake Vents:
(Within Lower 1/3 of Attic)
9
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
2,900
Code Required Method:
1/300 (EXCEPTION)
Calculation:
2,900 ÷ 300 = 9.67 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
9.67
Calculation:
9.67 x 144 = 1,392.48 sq. in. of Code Required Ventilation
Square Inches Provided:
(18 x 86.25) = 1,552.50 sq. in.
clay Tile Vents
Medium Profile (M)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 86.25 sq. in.
Figures based on independent evaluation reports.
Vent Solutions