4910 NW 113 Avenue Coral Springs, FL
Total Vents:
26
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
13
Low / Intake Vents:
(Within Lower 1/3 of Attic)
13
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
4,524
Code Required Method:
1/300 (EXCEPTION)
Calculation:
4,524 ÷ 300 = 15.08 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
15.08
Calculation:
15.08 x 144 = 2,171.52 sq. in. of Code Required Ventilation
Square Inches Provided:
(26 x 86.25) = 2,242.50 sq. in.
concrete Tile Vents
Medium Profile (M)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 86.25 sq. in.