Address:
9777 Caminito Joven San Diego, CA 92131
Total Vents:
14
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
7
Low / Intake Vents:
(Within Lower 1/3 of Attic)
7
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
2,300
Code Required Method:
1/300 (EXCEPTION)
Calculation:
2,300 ÷ 300 = 7.67 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
7.67
Calculation:
7.67 x 144 = 1,104.48 sq. in. of Code Required Ventilation
Square Inches Provided:
(14 x 87.75) = 1,228.50 sq. in.
clay Tile Vents
High Profile (S)
NET FREE VENTILATION AREA
1/8" Noncombustible, Corrosion-Resistant Wire Mesh 87.75 sq. in.
Figures based on independent evaluation reports.
Vent Solutions
Questions?