Total Vents:
162
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
81
Low / Intake Vents:
(Within Lower 1/3 of Attic)
81
Comp Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
12,100
Code Required Method:
1/150 (STANDARD)
Calculation:
12,100 ÷ 150 = 80.67 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
80.67
Calculation:
80.67 x 144 = 11,616.48 sq. in. of Code Required Ventilation
Square Inches Provided:
(162 x 72) = 11,664 sq. in.
Composition shingle
Low Profile (Tapered)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 72 sq. in.
Figures based on independent evaluation reports.