Total Vents:
18
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
9
Low / Intake Vents:
(Within Lower 1/3 of Attic)
9
Metal Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
2,603
Code Required Method:
1/300 (EXCEPTION)
Calculation:
2,603 ÷ 300 = 8.68 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
8.68
Calculation:
8.68 x 144 = 1,249.92 sq. in. of Code Required Ventilation
Square Inches Provided:
(18 x 78) = 1,404 sq. in.
Standing Seam metal
Low Profile (Tapered)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 78 sq. in.
Figures based on independent evaluation reports.