Total Vents:
152
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
76
Low / Intake Vents:
(Within Lower 1/3 of Attic)
76
Comp Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
15,500
Code Required Method:
1/150 (EXCEPTION)
Calculation:
15,500 ÷ 150 = 103.33 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
103.33
Calculation:
103.33 x 144 = 14,879.52 sq. in. of Code Required Ventilation
Square Inches Provided:
(152 x 98.75) = 15,010 sq. in.
synthetic Shake and Slate Vents
Low Profile (Tapered)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 98.75 sq. in.
Figures based on independent evaluation reports.