Address:
14079 W. RYAN ST., SYLMAR, CA. 91342
Total Vents:
6
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
3
Low / Intake Vents:
(Within Lower 1/3 of Attic)
3
Comp Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
372
Code Required Method:
1/150 (EXCEPTION)
Calculation:
372 ÷ 150 = 2.48 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
2.48
Calculation:
2.48 x 144 = 357.12 sq. in. of Code Required Ventilation
Square Inches Provided:
(6 x 72) = 432 sq. in.
Composition shingle
Low Profile (Tapered)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 72 sq. in.
Figures based on independent evaluation reports.
Vent Solutions