Address:
215 Belvidere, San Antonio, TX 78212
Total Vents:
18
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
9
Low / Intake Vents:
(Within Lower 1/3 of Attic)
9
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
1,688
Code Required Method:
1/150 (EXCEPTION)
Calculation:
1,688 ÷ 150 = 11.25 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
11.25
Calculation:
11.25 x 144 = 1,620 sq. in. of Code Required Ventilation
Square Inches Provided:
(18 x 98.75) = 1,777.50 sq. in.
clay Tile Vents
Low Profile (Flat)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 98.75 sq. in.
Figures based on independent evaluation reports.
Vent Solutions
Questions?