Address:
2001 Batello Drive, Venice, FL 34292
Total Vents:
280
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
140
Low / Intake Vents:
(Within Lower 1/3 of Attic)
140
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
25,000
Code Required Method:
1/150 (EXCEPTION)
Calculation:
25,000 ÷ 150 = 166.67 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
166.67
Calculation:
166.67 x 144 = 24,000.48 sq. in. of Code Required Ventilation
Square Inches Provided:
(280 x 86.25) = 24,150 sq. in.
concrete Tile Vents
Medium Profile (M)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 86.25 sq. in.
Figures based on independent evaluation reports.
Vent Solutions