430 SERENO PLACE, CAMARILLO, CA
Total Vents:
52
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
26
Low / Intake Vents:
(Within Lower 1/3 of Attic)
26
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
5,195
Code Required Method:
1/150 (EXCEPTION)
Calculation:
5,195 ÷ 150 = 34.63 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
34.63
Calculation:
34.63 x 144 = 4,986.72 sq. in. of Code Required Ventilation
Square Inches Provided:
(52 x 97.50) = 5,070 sq. in.
clay Tile Vents
High Profile (S)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 97.50 sq. in.
Figures based on independent evaluation reports.
Vent Solutions