Total Vents:
14
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
7
Low / Intake Vents:
(Within Lower 1/3 of Attic)
7
Comp Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
1,952
Code Required Method:
1/300 (EXCEPTION)
Calculation:
1,952 ÷ 300 = 6.51 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
6.51
Calculation:
6.51 x 144 = 937.44 sq. in. of Code Required Ventilation
Square Inches Provided:
(14 x 72) = 1,008 sq. in.
Composition shingle
Low Profile (Tapered)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 72 sq. in.
Figures based on independent evaluation reports.