Address:
22308 WHIRLAWAY CT
Total Vents:
24
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
12
Low / Intake Vents:
(Within Lower 1/3 of Attic)
12
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
4,200
Code Required Method:
1/300 (EXCEPTION)
Calculation:
4,200 ÷ 300 = 14 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
14
Calculation:
14 x 144 = 2,016 sq. in. of Code Required Ventilation
Square Inches Provided:
(24 x 87.75) = 2,106 sq. in.
clay Tile Vents
High Profile (S)
NET FREE VENTILATION AREA
1/8" Noncombustible, Corrosion-Resistant Wire Mesh 87.75 sq. in.
Figures based on independent evaluation reports.
Vent Solutions