Total Vents:
92
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
46
Low / Intake Vents:
(Within Lower 1/3 of Attic)
46
Comp Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
6,200
Code Required Method:
1/150 (EXCEPTION)
Calculation:
6,200 ÷ 150 = 41.33 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
41.33
Calculation:
41.33 x 144 = 5,951.52 sq. in. of Code Required Ventilation
Square Inches Provided:
(92 x 64.80) = 5,961.60 sq. in.
Composition shingle
Low Profile (Tapered)
NET FREE VENTILATION AREA
1/8" Noncombustible, Corrosion-Resistant Wire Mesh 64.80 sq. in.
Figures based on independent evaluation reports.
Vent Solutions