Address:
3325 Via Verde Ct, Calabasas CA
Total Vents:
100
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
50
Low / Intake Vents:
(Within Lower 1/3 of Attic)
50
Comp Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
7,500
Code Required Method:
1/150 (EXCEPTION)
Calculation:
7,500 ÷ 150 = 50 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
50
Calculation:
50 x 144 = 7,200 sq. in. of Code Required Ventilation
Square Inches Provided:
(100 x 72) = 7,200 sq. in.
Composition shingle
Low Profile (Tapered)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 72 sq. in.
Figures based on independent evaluation reports.
Vent Solutions
Questions?