Address:
4278 Navajo Ave, Toluca Lake, CA 91602
Total Vents:
24
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
12
Low / Intake Vents:
(Within Lower 1/3 of Attic)
12
Metal Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
1,900
Code Required Method:
1/150 (EXCEPTION)
Calculation:
1,900 ÷ 150 = 12.67 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
12.67
Calculation:
12.67 x 144 = 1,824.48 sq. in. of Code Required Ventilation
Square Inches Provided:
(24 x 78) = 1,872 sq. in.
Standing Seam metal
Low Profile (Tapered)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 78 sq. in.
Figures based on independent evaluation reports.
Vent Solutions
Questions?