Total Vents:
4
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
2
Low / Intake Vents:
(Within Lower 1/3 of Attic)
2
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
272
Code Required Method:
1/150 (EXCEPTION)
Calculation:
272 ÷ 150 = 1.81 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
1.81
Calculation:
1.81 x 144 = 260.64 sq. in. of Code Required Ventilation
Square Inches Provided:
(4 x 87.75) = 351 sq. in.
clay Tile Vents
High Profile (S)
NET FREE VENTILATION AREA
1/8" Noncombustible, Corrosion-Resistant Wire Mesh 87.75 sq. in.
Figures based on independent evaluation reports.