Total Vents:
44
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
22
Low / Intake Vents:
(Within Lower 1/3 of Attic)
22
Comp Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
6,576
Code Required Method:
1/300 (EXCEPTION)
Calculation:
6,576 ÷ 300 = 21.92 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
21.92
Calculation:
21.92 x 144 = 3,156.48 sq. in. of Code Required Ventilation
Square Inches Provided:
(44 x 72) = 3,168 sq. in.
Composition shingle
Low Profile (Tapered)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 72 sq. in.
Figures based on independent evaluation reports.
Vent Solutions
Questions?