Address:
24184 LOMA PRIETA AVE LOS GATOS, CA
Total Vents:
8
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
4
Low / Intake Vents:
(Within Lower 1/3 of Attic)
4
Metal Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
1,034
Code Required Method:
1/300 (EXCEPTION)
Calculation:
1,034 ÷ 300 = 3.45 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
3.45
Calculation:
3.45 x 144 = 496.80 sq. in. of Code Required Ventilation
Square Inches Provided:
(8 x 78) = 624 sq. in.
Standing Seam metal
Low Profile (Tapered)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 78 sq. in.
Figures based on independent evaluation reports.