4365 Holland Drive St. Pete Beach, FL 33706
Total Vents:
22
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
11
Low / Intake Vents:
(Within Lower 1/3 of Attic)
11
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
4,100
Code Required Method:
1/300 (EXCEPTION)
Calculation:
4,100 ÷ 300 = 13.67 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
13.67
Calculation:
13.67 x 144 = 1,968.48 sq. in. of Code Required Ventilation
Square Inches Provided:
(22 x 97.50) = 2,145 sq. in.
clay Tile Vents
High Profile (S)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 97.50 sq. in.
Figures based on independent evaluation reports.