Address:
2500 N HOUGHTON RD
Total Vents:
38
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
19
Low / Intake Vents:
(Within Lower 1/3 of Attic)
19
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
3,672
Code Required Method:
1/150 (EXCEPTION)
Calculation:
3,672 ÷ 150 = 24.48 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
24.48
Calculation:
24.48 x 144 = 3,525.12 sq. in. of Code Required Ventilation
Square Inches Provided:
(38 x 97.50) = 3,705 sq. in.
concrete Tile Vents
High Profile (S)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 97.50 sq. in.
Figures based on independent evaluation reports.
Vent Solutions
Questions?