Address:
3051 Jackson St., Oxnard, CA. 93033
Total Vents:
4
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
2
Low / Intake Vents:
(Within Lower 1/3 of Attic)
2
Comp Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
184
Code Required Method:
1/150 (EXCEPTION)
Calculation:
184 ÷ 150 = 1.23 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
1.23
Calculation:
1.23 x 144 = 177.12 sq. in. of Code Required Ventilation
Square Inches Provided:
(4 x 64.80) = 259.20 sq. in.
Composition shingle
Low Profile (Tapered)
NET FREE VENTILATION AREA
1/8" Noncombustible, Corrosion-Resistant Wire Mesh 64.80 sq. in.
Figures based on independent evaluation reports.
Vent Solutions
Questions?