Total Vents:
12
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
6
Low / Intake Vents:
(Within Lower 1/3 of Attic)
6
Comp Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
779
Code Required Method:
1/150 (EXCEPTION)
Calculation:
779 ÷ 150 = 5.19 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
5.19
Calculation:
5.19 x 144 = 747.36 sq. in. of Code Required Ventilation
Square Inches Provided:
(12 x 64.80) = 777.60 sq. in.
Composition shingle
Low Profile (Tapered)
NET FREE VENTILATION AREA
1/8" Noncombustible, Corrosion-Resistant Wire Mesh 64.80 sq. in.
Figures based on independent evaluation reports.