Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
2,200
Code Required Method:
1/300 (EXCEPTION)
Calculation:
2,200 ÷ 300 = 7.33 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
7.33
Calculation:
7.33 x 144 = 1,055.52 sq. in. of Code Required Ventilation
Square Inches Provided:
(14 x 86.25) = 1,207.50 sq. in.
concrete Tile Vents
Medium Profile (M)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 86.25 sq. in.
Figures based on independent evaluation reports.