Total Vents:
6
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
3
Low / Intake Vents:
(Within Lower 1/3 of Attic)
3
Comp Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
704
Code Required Method:
1/300 (EXCEPTION)
Calculation:
704 ÷ 300 = 2.35 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
2.35
Calculation:
2.35 x 144 = 338.40 sq. in. of Code Required Ventilation
Square Inches Provided:
(6 x 64.80) = 388.80 sq. in.
Composition shingle
Low Profile (Tapered)
NET FREE VENTILATION AREA
1/8" Noncombustible, Corrosion-Resistant Wire Mesh 64.80 sq. in.
Figures based on independent evaluation reports.