Total Vents:
86
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
43
Low / Intake Vents:
(Within Lower 1/3 of Attic)
43
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
15,300
Code Required Method:
1/300 (EXCEPTION)
Calculation:
15,300 ÷ 300 = 51 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
51
Calculation:
51 x 144 = 7,344 sq. in. of Code Required Ventilation
Square Inches Provided:
(86 x 86.25) = 7,417.50 sq. in.
concrete Tile Vents
Medium Profile (M)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 86.25 sq. in.
Figures based on independent evaluation reports.